Message ID: 54     Entry time: Wed Mar 22 15:25:00 2023
Author: Shane 
Type: Update 
Category: General 
Subject: Clean room recertification particle counts  
Attached are the five zone particle measurements for the clean room now that the fan speeds have been set to MEDIUM. 2 min sample time, 3 samples per zone. The occupied clean room measurements were unusual in that they generally got larger towards minute 6 instead of settling and going to zero, and for this reason didn't stay beneath the class 5 requirement at the end of the samples. The unoccupied counts look more similar to what was expected, and generally settle under the class five requirement.
Attachment 1: counts3.22.23.pdf  961 kB  | Hide | Hide all